Services crossing this level's walls, floors and roofs, grouped into proposed openings and judged by the structural rule book. Nothing below was cut without explicit approval, and everything that could not be processed is listed with its reason — a host silently skipped is the one thing this report must never do.
6 crossing services · thickness 300 mm · fire rating EI120 · SHEAR / CORE
| Mark | Size | Services | Findings | |
|---|---|---|---|---|
P01-MEC-019 |
490 x 290 mm | Pipe 110 #413002, Pipe 75 #413009 |
|
|
P01-MEC-020 |
690 x 450 mm | Duct 400x250 #412031 |
|
|
P01-MEC-021 |
925 x 450 mm | Duct 300x250 #412044, Duct 250x200 #412057 |
|
|
P01-MEC-022 |
340 x 340 mm | Pipe 160 #413044 |
|
9 crossing services · thickness 200 mm · fire rating EI60
| Mark | Size | Services | Findings | |
|---|---|---|---|---|
P01-MEC-023 |
600 x 400 mm | Duct 400x200 #412108 |
|
|
P01-MEC-024 |
675 x 290 mm | Pipe 110 #413061, Pipe 63 #413077, Pipe 50 #413084 |
|
|
P01-MEC-004 |
700 x 500 mm | Duct 500x300 #412121 |
|
|
P01-MEC-025 |
340 x 340 mm | Pipe 160 #413096 |
|
|
P01-ELE-006 |
650 x 310 mm | CableTray 450x100 #418220 |
|
|
P01-MEC-026 |
730 x 450 mm | Duct 250x250 #412140, Pipe 90 #413110 |
|
5 crossing services · thickness 250 mm
| Mark | Size | Services | Findings | |
|---|---|---|---|---|
P01-MEC-027 |
800 x 600 mm | Duct 600x400 #412210 |
|
|
P01-MEC-028 |
950 x 600 mm | Duct 750x400 #412224 |
|
|
P01-MEC-029 |
200 x 200 mm | Pipe 90 #413140 |
|
|
P01-MEC-030 |
200 x 200 mm | Pipe 90 #413147 |
|
Hosts Opes could not work on, each with its reason. These are findings, not noise.
| Host | Reason |
|---|---|
| Walls id 884902 (Curtain Wall - Atrium Screen) | Curtain wall — cannot host a face-based cutting family. |
| Walls id 885140 (Stacked Wall - Lift Lobby) | Stacked wall — a multi-element composition, out of scope for v1. |
| Floors id 902580 (Slab - RC 200) | The host's solid geometry could not be read, so nothing could be tested against it. |
Someone else has these checked out. Opes never takes ownership (it would write into the central file) — ask the owner to relinquish and run again.
| Host | Reason |
|---|---|
| Walls id 884955 (Core Wall - RC 250) | Owned by m.oduya. Opes does not take ownership — ask them to relinquish. |
The sync pass compared every sealed opening against the model as it is now. Stale means its host or services changed since it was cut; orphaned means they are gone; a locked opening is never updated — its discrepancy is an RFI, not an edit.
| Host | Reason |
|---|---|
| P01-MEC-004 | its services' geometry changed since it was cut |
| P01-MEC-012 | its host's geometry changed since it was cut |
| P01-ELE-002 | a service it was cut for no longer exists in its link |
| P01-MEC-009 | its host and its services changed since it was cut — but it is LOCKED (built on site): raise an RFI, Opes will not touch it |
| P01-MEC-015 | a link is unloaded (or a ref unreadable) — whether this opening is still right could NOT be checked. Load the links and sync again. |
| P01-MEC-016 | a link is unloaded (or a ref unreadable) — whether this opening is still right could NOT be checked. Load the links and sync again. |
| P01-ELE-004 | a link is unloaded (or a ref unreadable) — whether this opening is still right could NOT be checked. Load the links and sync again. |
| P01-MEC-002 | everything matches again (was Stale) — recovered |
| Mark | Host | Outcome | Evidence | |
|---|---|---|---|---|
P01-MEC-023600 x 400 mm |
Wall Interior - Blockwork 200 (id 884671) | Placed and cut, verified | host=Wall id 884671 (Interior - Blockwork 200) vol before=7.2 m3 after=7.152 m3 dropped=0.048 m3 expected=0.048 m3 cuttingVoids=3 relation=True landedOnAskedHost=True | |
P01-MEC-024675 x 290 mm |
Wall Interior - Blockwork 200 (id 884671) | Placed and cut, verified | host=Wall id 884671 (Interior - Blockwork 200) vol before=7.152 m3 after=7.11285 m3 dropped=0.03915 m3 expected=0.03915 m3 cuttingVoids=4 relation=True landedOnAskedHost=True | |
P01-MEC-004700 x 500 mm |
Wall Interior - Blockwork 200 (id 884671) | Placed and cut, verified Replaced the drifted instance (same identity, same mark). |
host=Wall id 884671 (Interior - Blockwork 200) vol before=7.11285 m3 after=7.04285 m3 dropped=0.07 m3 expected=0.07 m3 cuttingVoids=5 relation=True landedOnAskedHost=True | |
P01-MEC-025340 x 340 mm |
Wall Interior - Blockwork 200 (id 884671) | Cut, but landed on a different host The instance landed on a different host than the one asked for; the cut on the asked host verified. Flagged in its record. |
host=Wall id 884671 (Interior - Blockwork 200) vol before=7.04285 m3 after=7.01973 m3 dropped=0.02312 m3 expected=0.02312 m3 cuttingVoids=6 relation=True landedOnAskedHost=False | |
P01-ELE-006650 x 310 mm |
Wall Interior - Blockwork 200 (id 884671) | Placed and cut, verified | host=Wall id 884671 (Interior - Blockwork 200) vol before=7.01973 m3 after=6.985072 m3 dropped=0.034658 m3 expected=0.0403 m3 cuttingVoids=7 relation=True landedOnAskedHost=True | |
P01-MEC-026730 x 450 mm |
Wall Interior - Blockwork 200 (id 884671) | Placed and cut, verified | host=Wall id 884671 (Interior - Blockwork 200) vol before=6.985072 m3 after=6.919372 m3 dropped=0.0657 m3 expected=0.0657 m3 cuttingVoids=8 relation=True landedOnAskedHost=True | |
P01-MEC-027800 x 600 mm |
Floor Slab - RC 250 (id 902114) | Placed and cut, verified | host=Floor id 902114 (Slab - RC 250) vol before=40.5 m3 after=40.38 m3 dropped=0.12 m3 expected=0.12 m3 cuttingVoids=2 relation=True landedOnAskedHost=True | |
P01-MEC-029200 x 200 mm |
Floor Slab - RC 250 (id 902114) | Placed and cut, verified | host=Floor id 902114 (Slab - RC 250) vol before=40.38 m3 after=40.37 m3 dropped=0.01 m3 expected=0.01 m3 cuttingVoids=3 relation=True landedOnAskedHost=True | |
P01-MEC-030200 x 200 mm |
Floor Slab - RC 250 (id 902114) | Placed and cut, verified | host=Floor id 902114 (Slab - RC 250) vol before=40.37 m3 after=40.36 m3 dropped=0.01 m3 expected=0.01 m3 cuttingVoids=4 relation=True landedOnAskedHost=True | |
P01-MEC-019490 x 290 mm |
Wall Core Wall - RC 300 (id 884213) | Skipped — prohibited, no override | ||
P01-MEC-020690 x 450 mm |
Wall Core Wall - RC 300 (id 884213) | Skipped — prohibited, no override | ||
P01-MEC-021925 x 450 mm |
Wall Core Wall - RC 300 (id 884213) | Skipped — prohibited, no override | ||
P01-MEC-022340 x 340 mm |
Wall Core Wall - RC 300 (id 884213) | Skipped — prohibited, no override | ||
P01-MEC-028950 x 600 mm |
Floor Slab - RC 250 (id 902114) | Skipped — prohibited, no override |